Emergency Responder Radio Coverage
Per IFC 510 Emergency Responders Radio Coverage the follow buildings will require a survey as outlined below:
-
For any structure with an overall square footage of 12,000 square feet
-
For any structure with a height of 30’ or more above grade level
-
For any structure with a level below grade
-
For any structure determined to be of concern of proper radio communication, CJCFPD can request a signal strength study to be completed
Testing with results must be shown to have acceptable emergency radio coverage. If that test fails, a TCO may be signed with an obligation to complete within six months. If determined through testing an in-building emergency radio communication enhancement system is required, that system…
-
-
Shall be listed for that use (this applies to all systems and components)
-
System design, installation, qualification of personnel, and acceptance testing must follow the current adopted IFC 510 and NFPA 72
-
More Testing Information…
-
A field test will be performed by CJC personnel at the time of CO utilizing CJC portable two-way communications. If that test fails, a TCO may be signed with an obligation to complete enhancement within six months
-
The system must be monitored through the building’s fire alarm system for loss of power; failure of the battery charger; low-battery capacity indication when 70% of the 12-hour operating capacity has been depleted; malfunction of the donor antenna and active RF-emitting device(s); and failure of any critical system components and provide either an audible warning or “trouble”
-
The system performance and reliability must be tested on installation and maintained operational at all times
-
An annual inspection is also required
-
To learn more about why this requirement exists, click here